LPD exempt

The Hong Kong Building Energy Code version 2012 rev1 and 2015 Lighting Power Density (LPD) requirement does NOT apply where the room lighting load does not exceed 100 watt (2012 rev1 page 13) and 70 watt  (2015 page 14) respectively.

2015-lpd 2012-lpd

by implication the target is the TOTAL power (lighting and control gear).  So what does that mean? for BEC 2015, it means a store room with total power is less than 70w you are not required to comply with the 9w/sqm LPD or the lighting control requirement.